HOME > Product > Cabinet Air Conditioner > Electrical Cabinet Dehumidifier
Electrical Cabinet Dehumidifier
• Dehumidification capacity: 230g/h
• Installation: Flange door mount
• Communication: RS485
• Rated input power: 230VAC(50/60Hz)
Description
HOP series industrial dehumidifiers are specially designed for controlling humidity in industrial cabinets. It is particularly suitable for solving the problem of condensed water easily generated on the liquid cooling plate of the energy storage system using liquid cooling temperature control solution. The dehumidifier adopts AC power supply design, integrated ultra-thin structure, door-mounted design, and high energy efficiency ratio, providing a safe, reliable, efficient and energy-saving dehumidification solution to solve the humidity problem of industrial cabinet system.
Application
Cabinet and enclosure in high humidity environment.

| Model | HOP DH0150D |
| Working environment temperature | 18℃~45℃ |
| Working environment humidity | 5~95%RH |
| Rated input power | 230VAC(50/60HZ) |
| Rated operating condition (30 °C 80% RH) dehumidification capacity | 230g/h |
| Rated operating (30 °C 80% RH) input power condition | 100W |
| Rated operating condition (30 °C 80% RH) input current | 0.4A |
| Worst operating condition (45 °C 95% RH) input power | 180W |
| Worst operating condition (45 °C 95% RH) input current | 0.8A |
| Maximum exhaust pressure | 2.0MPa |
| Maximum suction pressure | 0.77MPa |
| MCA | 1A |
| MOP | 3A |
| FAN MOC | 0.215A |
| Surface treatment | Electrostatic spraying |
| Refrigerant | R513A 130g |
| Compressor power conversion current | 6A |
| Box dimensions (width * height * depth) | 550*400*70mm |
| Weight | 10kg |
| Installation method | Flange Door decoration |
Functions
(1) According to relative humidity control
The startup conditions are met: the humidity inside the cabinet (locally read or issued by the user) is > the set point of relative humidity (40% -80 can be set, default 40%), and the lower limit of dehumidification temperature (-40-5 °C can be set, default 5 °C) ≤ return air temperature ≤ upper limit of dehumidification temperature (50-80 °C can be set, default 50 °C) and lasts for 15 seconds;
Stop condition: The humidity inside the cabinet is ≤ relative humidity set point – relative dehumidification hysteresis setting (1% -20% can be set, default is 20o), and it lasts for 30 seconds.
(2) Control based on dew point temperature
When the dew point temperature (calculated based on local or customer issued relative humidity and return air temperature) is > the dew point dehumidification temperature setting value (-40-120 °C can be set, default 13 °C), and the current temperature lower limit (-40-5 °C can be set, default 5 C) ≤ return air temperature ≤ dehumidification temperature upper limit (50-80 °C can be set, default 50 C) and lasts for 15 seconds;
Stop condition: When the dew point temperature is < the dew point dehumidificationtemperature set value – dew point hysteresis set value (1-20 °C can be set, default is 6 °C), and lasts for 30 seconds.
Features
More Than 10 years Design Service Life