Enclosure Cooling Unit
Enclosure Cooling Systems, Units & Solutions
HOP’s sealed enclosure cooling systems, units & solutions effectively dissipate heat from sealed electrical and electronic enclosures operating in indoor, outdoor and other types of environments.
They are maintenance-free and function without problems even in heavily polluted ambient air. The hermetically sealed cooling circuit ensures high efficiency and safety during operation.
Enclosure Cooling for Harsh Environments
Our enclosure cooling units are applicable in diverse industries including Industrial Automation, Food Processing, Chemical, Petrochemical, Wastewater Treatment, and Telecommunications.
Whether in cold, wet, dusty air or extreme heat, Hop outdoor air conditioners are ideal for harsh environments. The operating temperature of -40°C to 55°C, an IP56 protection class, integrated condensate evaporation, enclosure heater and aluminium filter, make these cooling units suitable for various applications.
Ideal closed-loop cooling solutions for your specific application
Chengdu Hop air conditioners deliver reliable enclosure cooling in demanding environments, including industrial automation, telecommunications, waste water treatment, material handling, security and defense systems, and more. Hop air conditioners are available in a variety of standard configurations with modifications available to offer a broad range of cooling solutions. All developed and tested to the highest standards.
The next-generation cooling technology, Hop Remote Access Control, is available as a factory-installed option for monitoring and maintenance across your entire network of Hop air conditioners. Get the intelligent, energy-efficient, low-noise, reliable cooling systems you need to meet your specific requirements.
Selecting the right enclosure cooling unit
Selecting the right enclosure cooling unit (air conditioner, heat exchanger, or vortex cooler) is critical to protect sensitive electronics from overheating, humidity, dust, and contaminants. Here’s a step-by-step guide focusing on key factors:
1. Calculate Internal Heat Load (Most Critical!)
- Sources: Drives, PLCs, power supplies, servers, lighting, motors.
- Calculate: Add up the power consumption (Watts) of all heat-generating components inside the enclosure. (Power in Watts = Heat in Watts).
- Rule of Thumb (Quick Estimate): If exact specs are unknown, estimate 10-15% of the total installed electrical load as heat, but always prefer exact calculations.
2. Determine Enclosure Size & Target Internal Temperature
- Enclosure Dimensions: Note height, width, depth (mm or inches).
- Target Internal Temp (T_int): What max temperature must the electronics stay below? (e.g., 35°C, 40°C). Must be above the dew point to avoid condensation.
- Maximum Ambient Temp (T_amb): What is the highest outside air temperature surrounding the enclosure? (e.g., 45°C in a factory). Consider seasonal peaks.
3. Assess Ambient Environment
- Clean/Dirty? Is the environment dusty, oily, or corrosive? (Critical for filter/coil choice).
- Humidity Level? High humidity increases condensation risk.
- Sun Exposure? Direct sunlight adds significant radiant heat load (add 10-20% to heat load calculation).
- Altitude? Higher altitudes reduce air density and cooling capacity (derating needed above ~1000m/3300ft).
4. Choose the Right Cooling Technology
Enclosure Air Conditioners (Compressor-Based):
- Best For: High heat loads, high ambient temps, environments requiring strict temperature/humidity control, dirty/outdoor locations.
- Pros: Cools below ambient, dehumidifies effectively.
- Cons: Highest cost, highest energy use, requires refrigerant, more maintenance.
Air-to-Air Heat Exchangers:
- Best For: Moderate heat loads, clean environments, ambient temps higher than target internal temp only by a small margin, where sealing the enclosure is beneficial.
- Pros: Sealed enclosure (no dust/moisture ingress), low energy use, low maintenance.
- Cons: Cannot cool below ambient, limited cooling capacity, requires T_amb < T_int.
Fans & Filter Kits (Ventilation):
- Best For: Very low heat loads, environments where ambient air is clean, cool, and dry enough to use directly.
- Pros: Lowest cost, simplest installation, low energy.
- Cons: No temperature control, no sealing (dust/humidity ingress), only works if T_amb < T_int.
Technology Comparison:
| Feature | Air Conditioner | Heat Exchanger | Fans |
| Cool Below Ambient | Yes | No | No |
| Dehumidifies | Yes | No (Seals) | No |
| Seals Enclosure | Yes | Yes | No |
| Max Heat Load | High (kW+) | Medium (~1.5kW) | Very Low |
| Energy Efficiency | Low-Medium | High | High |
| Noise Level | Medium | Low | Low-Medium |
| Maintenance | Higher (Filters, Refrig) | Low (Filters) | Low (Filters) |
| Ideal Environment | Dirty/Humid/Hot/Outdoor | Clean/Moderate Temp | Clean/Cool/Dry |
5. Determine Required Cooling Capacity
- Use the formula: Q_cooling = Q_internal + Q_solar + Q_other
- Q_internal: Your calculated heat load (Watts).
- Q_solar: Add 10-20% of Q_internal for direct sun exposure, or calculate precisely (surface area x solar irradiance x absorption coefficient).
- Q_other: Conduction through walls (usually minor unless large ΔT).
- Add Safety Margin: Add 10-25% to the total calculated load for aging, unforeseen loads, and derating (especially at high altitude or high ambient temps). This final value is your minimum required cooling capacity (in Watts or BTU/hr – 1kW ≈ 3412 BTU/hr).
6. Consider Physical & Installation Factors
- Mounting: Top, side, recessed? Ensure space and structural support.
- Electrical Supply: Voltage (120V, 230V, 480V), phase, frequency, available power. Compressor units need significant startup current.
- Condensate Drain: Air conditioners produce water – plan drainage (gravity or pump).
- Airflow Path: Ensure intake/exhaust vents are unobstructed. Avoid recirculation.
- NEMA/IP Rating: Match the cooling unit’s ingress protection rating to the environment (e.g., NEMA 12/4/4X for indoor industrial, NEMA 3R/4/4X for outdoor). IP54/IP55 common.
7. Control & Monitoring Needs
- Basic Thermostat: On/Off control sufficient?
- Digital Controller: Needed for precise temp/humidity control, alarms, communication (Modbus, Ethernet/IP)?
- Remote Monitoring/Alarming: Essential for critical applications?
8. Maintenance Requirements
- Filters: How often do they need cleaning/replacement? Is access easy?
- Coils: Need periodic cleaning (especially in dirty environments – ACs & Heat Exchangers).
- Refrigerant: ACs may need eventual recharging.
9. Budget Considerations (TCO)
- Initial Cost: Vortex < Fans < Heat Exchangers < Air Conditioners.
- Operating Cost: Fans ≈ Heat Exchangers < Air Conditioners << Vortex Coolers (compressed air is expensive).
- Maintenance Cost: Fans ≈ Vortex < Heat Exchangers < Air Conditioners.
Actionable Summary Checklist
✅ Calculate Total Internal Heat Load (Watts).
✅ Define Target Internal Temp & Max Ambient Temp.
✅ Assess Environment (Clean/Dirty? Humid? Sunny?).
✅ Select Cooling Technology based on Steps 1-3 & comparison table.
✅ Calculate Required Cooling Capacity (add safety margin!).
✅ Check Physical Fit: Mounting, NEMA/IP rating, power, drain.
✅ Specify Controls: Thermostat vs. digital controller.
✅ Verify Maintenance Plan: Filter access, cleaning schedule.
✅ Compare TCO: Initial cost + operating cost (energy/air) + maintenance.
Pro Tip: Use online sizing tools from reputable manufacturers ( Rittal, Schneider, Hoffman) – input your data for recommendations, but always verify with manual calculations. When in doubt, consult a thermal management specialist or the manufacturer’s technical support. Choosing correctly prevents costly downtime and equipment failure!